EPA 608 HVAC — Interactive Formula Workbench & Cheat Sheet
Enter your own problem numbers to see every step of the math—not just a final answer.
EPA 608 Annualized Leak Rate Calculator (40 CFR § 82.157)
Calculated Annual Leak Rate
27.0% / year
EXCEEDS 20% — 30-DAY REPAIR REQUIRED
Step-by-step: (8 ÷ 120) × (365 ÷ 90) × 100 = 27.04%
EPA 608 Required Evacuation Vacuum Lookup (Table 1)
Post-Nov 15, 1993 Equipment (Most Tested)
15 inHg vacuum
Pre-Nov 15, 1993 Legacy Equipment
4 inHg vacuum
High-pressure appliances other than R-22 holding 200 lbs or more.
Exam Formula Reference Sheet (EPA-608)
Annualized Leak Rate Formula (40 CFR § 82.157)
Leak Rate (%) = (lbs Added ÷ Full Charge lbs) × (365 ÷ Days Since Last Add) × 100
- • lbs Added = pounds of refrigerant added during the service call
- • Full Charge = normal full operating charge of the appliance (lbs)
- • Days Since Last Add = calendar days elapsed since previous refrigerant addition (use 365 if first addition in a year)
Worked Example: A 100-lb commercial rack receives 8 lbs after 90 days: (8 ÷ 100) × (365 ÷ 90) × 100 = 32.4% → Exceeds the 20% commercial limit! Repair required within 30 days.
Exam Trap Tip: Watch the trigger thresholds: 10% Comfort Cooling, 20% Commercial Refrigeration, 30% Industrial Process Refrigeration.
EPA Section 608 Required Evacuation Levels (Post-Nov 15, 1993 Equipment)
| Appliance Type | Charge Size | Required Vacuum (Post-1993) |
|---|---|---|
| HCFC-22 (R-22) Appliance | < 200 lbs | 0 psig |
| HCFC-22 (R-22) Appliance | ≥ 200 lbs | 10 inHg vacuum |
| Other High-Pressure (R-410A, R-404A, R-134a) | < 200 lbs | 10 inHg vacuum |
| Other High-Pressure (R-410A, R-404A, R-134a) | ≥ 200 lbs | 15 inHg vacuum |
| Very High-Pressure (R-13, R-503) | Any size | 0 psig |
| Low-Pressure Chiller (R-123, R-11) | Any size | 25 mmHg absolute |
Annual Leak Repair Trigger Thresholds (Appliances ≥ 50 lbs)
| Equipment Category | Max Annual Leak Rate | Repair Window |
|---|---|---|
| Comfort Cooling (HVAC) | 10% | 30 days |
| Commercial Refrigeration | 20% | 30 days |
| Industrial Process Refrigeration (IPR) | 30% | 30 days (120 days if industrial shutdown required) |