EPA Section 608 Universal Certification Practice Exam
Master Core, Type I, Type II, and Type III refrigerant regulations, evacuation vacuum levels, leak-repair thresholds, and A2L safety rules without memorizing static answer keys.
Core Section (Mandatory)
Ozone depletion, Clean Air Act venting ban, the 3 R's (Recover/Recycle/Reclaim), DOT cylinders, and A2L flammable refrigerant basics. You must pass Core to earn any certification.
Type I — Small Appliances
Factory-charged, hermetically sealed appliances containing 5 pounds or less of refrigerant (domestic refrigerators, window ACs, vending machines).
Type II — High-Pressure Appliances
High-pressure and very high-pressure equipment containing more than 5 lbs of refrigerant (residential split systems, commercial reach-ins, R-410A, R-22, R-454B).
Type III — Low-Pressure Appliances
Centrifugal chillers and low-pressure appliances operating below atmospheric pressure (R-123, R-11, R-1233zd).
EPA Section 608 Required Evacuation Levels (Post-Nov 15, 1993 Equipment)
The single most tested table across Type II and Type III exams.
| Appliance Type | Charge Size | Required Vacuum (Post-1993) |
|---|---|---|
| HCFC-22 (R-22) Appliance | < 200 lbs | 0 psig |
| HCFC-22 (R-22) Appliance | ≥ 200 lbs | 10 inHg vacuum |
| Other High-Pressure (R-410A, R-404A, R-134a) | < 200 lbs | 10 inHg vacuum |
| Other High-Pressure (R-410A, R-404A, R-134a) | ≥ 200 lbs | 15 inHg vacuum |
| Very High-Pressure (R-13, R-503) | Any size | 0 psig |
| Low-Pressure Chiller (R-123, R-11) | Any size | 25 mmHg absolute |
Annual Leak Repair Trigger Thresholds (Appliances ≥ 50 lbs)
Exceeding these rates mandates repair within 30 days + verification tests.
| Equipment Category | Max Annual Leak Rate | Repair Window |
|---|---|---|
| Comfort Cooling (HVAC) | 10% | 30 days |
| Commercial Refrigeration | 20% | 30 days |
| Industrial Process Refrigeration (IPR) | 30% | 30 days (120 days if industrial shutdown required) |
Frequently Asked Questions — EPA 608 HVAC
What score do I need to pass the EPA 608 Universal Exam?
You must score at least 70% (18 correct answers out of 25 questions) on EACH individual section—Core, Type I, Type II, and Type III. Passing Core is mandatory; if you fail Core, you cannot earn Type I, II, or III until Core is passed.
Does EPA Section 608 certification expire?
No. Once earned, your EPA Section 608 certification never expires and requires no renewal fees or continuing education credits. However, technicians are legally responsible for keeping up with updated rules such as A2L flammable refrigerant handling and revised leak-rate thresholds.
Are R-32 and R-454B (A2L refrigerants) on the EPA 608 exam?
Yes. Modern EPA 608 exams include questions on ASHRAE Standard 34 safety classifications (A1 vs. A2L vs. A3), safe handling of mildly flammable A2L refrigerants, recovery equipment ratings, and cylinder identification.
Is the EPA 608 Type I exam open-book or closed-book?
Type I can be taken open-book (online/unproctored) through select EPA-approved certifying organizations, whereas Core, Type II, Type III, and Universal exams MUST be taken closed-book under live proctoring.
HVAC technicians, appliance repair pros, refrigeration mechanics, and facility maintenance techs who open or service regulated refrigerant circuits.