Cylinders & Safety
CARD 1 / 16
HARD NUMBER PROMPT

Maximum safe liquid fill capacity for a DOT recovery cylinder?

40 CFR § 82.156Click or Space to reveal

Complete Hard Numbers Cheat List (EPA-608)

Maximum safe liquid fill capacity for a DOT recovery cylinder?
80% liquid capacity
DOT recovery cylinder hydrostatic re-test interval?
Every 5 years
Purity standard required before reselling reclaimed refrigerant to a new owner?
AHRI Standard 700
When did the federal EPA venting ban take effect for CFC/HCFCs vs. substitutes (HFCs)?
July 1, 1992 (CFC/HCFC) • Nov 15, 1995 (HFCs)
ASHRAE 34 safety classes for R-410A, R-32/R-454B, R-123, and R-290/R-600a?
R-410A: A1 • R-32/454B: A2L • R-123: B1 • R-290/600a: A3
Max distance from hose end for manual shut-off valves on recovery hoses?
Within 12 inches of hose end
Type I recovery requirement (post-Nov 15, 1993 equipment): Operating vs. Dead compressor?
90% operating / 80% dead (or 4 inHg)
Max factory refrigerant charge defining a Type I Small Appliance?
5 pounds or less (factory-charged & hermetically sealed)
Annual leak repair thresholds (systems ≥ 50 lbs): Comfort / Commercial / IPR?
10% / 20% / 30%
High-pressure appliance (non-R22, e.g., R-410A/R-404A) < 200 lbs vs. ≥ 200 lbs?
10 inHg (< 200 lbs) • 15 inHg (≥ 200 lbs)
Annual leak percentage that requires filing a Chronic Leaker Report with the EPA?
125% or more of full charge in a calendar year
Minimum retention period for EPA service/leak records on ≥ 50 lb systems?
3 years
Low-pressure chiller (R-123) max nitrogen leak-test pressure & rupture disc rating?
10 psig max test / 15 psig rupture disc
Post-1993 evacuation standard for Type III low-pressure chillers?
25 mmHg absolute
Minimum saturation temperature before introducing LIQUID R-123 into an evacuated chiller?
Above 32°F (36°F safe target • ~16.9 inHg vacuum)
ASHRAE Permissible Exposure Limit (PEL) for R-123 (Class B1)?
50 ppm (8-hour TWA)
Deck Mastery
0%0 of 16 locked

Tip: Drill these exact thresholds the night before and 15 minutes before walking into the proctored exam center.